Bugtraq mailing list archives
RE: APC 9606 SmartSlot Web/SNMP management card "backdoor" - Telnet can't be disabled.
From: "Miskell, Craig" <Craig.Miskell () agresearch co nz>
Date: Fri, 20 Feb 2004 10:27:31 +1300
The device appears to need a "restart for this change to take effect" (to quote a phrase from another OS). We have a 9604 (which, incidentally, appears to have the same default password, although the details once logged in are different), and telnet wasn't disabled until I had logged in via telnet and logged out again. The device warmstarted when I logged out, and telnet was subsequently truly disabled. HTH, Craig Miskell
-----Original Message----- From: David Monosov [mailto:david.monosov () futureinquestion net] Sent: Friday, 20 February 2004 4:14 a.m. To: bugtraq () securityfocus com Subject: APC 9606 SmartSlot Web/SNMP management card "backdoor" - Telnet can't be disabled. To your attention: This comes from limited experience with one version of the 9606 firmware (v3.0.3) on MasterSwitch 9xxx series, tested across many of the devices: Although provided an option to disable telnet administratively via the Web interface as well as the Telnet interface itself - telnet does *NOT* actually gets disabled. It disables itself for a matter of approx +/- 20 seconds, and comes back as if nothing ever happened. Repeating attempts to disable telnet access are futile. The only effective method of preventing possible exploitation seems to be filtering port 23 on the network level. This seems to be another firmware issue. Please check your APC's using 9606, your sense of security from disabling telnet might be false :( --- David 'wEEkAY' Monosov david dot monosov at futureinquestion dot net
======================================================================= Attention: The information contained in this message and/or attachments from AgResearch Limited is intended only for the persons or entities to which it is addressed and may contain confidential and/or privileged material. Any review, retransmission, dissemination or other use of, or taking of any action in reliance upon, this information by persons or entities other than the intended recipients is prohibited by AgResearch Limited. If you have received this message in error, please notify the sender immediately. =======================================================================
Current thread:
- APC 9606 SmartSlot Web/SNMP management card "backdoor" - Telnet can't be disabled. David Monosov (Feb 19)
- Re: APC 9606 SmartSlot Web/SNMP management card "backdoor" - Telnet can't be disabled. Keith Clifton (Feb 19)
- <Possible follow-ups>
- RE: APC 9606 SmartSlot Web/SNMP management card "backdoor" - Telnet can't be disabled. Miskell, Craig (Feb 19)