Re: Re[2]: telehouse - 25 broadway
From: Leo Bicknell <bicknell () ufp org>
Date: Sun, 16 Sep 2001 10:46:35 -0400
On Sat, Sep 15, 2001 at 08:56:10PM -0700, Sean Donelan wrote:
But I would like to point out, no one regularly runs their generators for 48+ hours as part of a normal test. In addition, most standby generators are fitted only for "limited" duration runs. You should expect problems during any extended run of a generator plant. I'm a bit surprised that 25 Broadway and 32 Old Slip are the only ones we've heard about.
I think "limited" here is a bit misleading. Most of these engines are continuous duity rated, which means within the bounds of maintenance items (oil changes, gasket changes, and other routine maintenance) they can run non-stop. Most gensets are essentially the same components that power diesel-electric locomotives that routinely run for weeks at a time without shutdown. Here in ice storm country every few years power is out for 3-4 days in some areas after bad storms. Generators routinely run for 3-4 days and cause no concern over their condition, other than to move up routine maintenance due to the additional run time. I suspect dust is going to be the largest problem for all generators in the area. It will reduce radiator effectiveness, wear on exteral parts (fans and the like), clog air and oil cleaners. Again, these devices are made for some fairly harsh enviornments so 48 hours is no concern, I would think expecting 2 weeks of reliable power if they are attended to even in these conditions is reasonable. That said, generators should always be at least N+1, as they are large, complex mechanical devices. -- Leo Bicknell - bicknell () ufp org Systems Engineer - Internetworking Engineer - CCIE 3440 Read TMBG List - tmbg-list-request () tmbg org, www.tmbg.org
Current thread:
- Re: telehouse - 25 broadway, (continued)
- Re: telehouse - 25 broadway JC Dill (Sep 15)
- Re: telehouse - 25 broadway Alex Rubenstein (Sep 15)
- Re[2]: telehouse - 25 broadway Joe McGuckin (Sep 15)
- Re: Re[2]: telehouse - 25 broadway Sean Donelan (Sep 15)
- Re: Re[2]: telehouse - 25 broadway Brian Whalen (Sep 15)
- Re: Re[2]: telehouse - 25 broadway Gwendolynn ferch Elydyr (Sep 16)
- Re: Re[2]: telehouse - 25 broadway mike harrison (Sep 16)
- Re: Re[2]: telehouse - 25 broadway Brian Whalen (Sep 15)
- Re: Re[2]: telehouse - 25 broadway David Lesher (Sep 16)
- Re: Re[2]: telehouse - 25 broadway JC Dill (Sep 16)
- Re: Re[2]: telehouse - 25 broadway kevin pop account (Sep 16)
- Re: Re[2]: telehouse - 25 broadway Leo Bicknell (Sep 16)
- Re: Re[2]: telehouse - 25 broadway Charles Sprickman (Sep 16)
- Re: Re[2]: telehouse - 25 broadway Alex Rubenstein (Sep 16)
- generator cooling (Re: Re[2]: telehouse - 25 broadway) E.B. Dreger (Sep 16)
- Re: generator cooling (Re: Re[2]: telehouse - 25 broadway) Alex Rubenstein (Sep 16)
- Re: Re[2]: telehouse - 25 broadway Leo Bicknell (Sep 16)
- Now:Power/Generators (Was: Re[2]: telehouse - 25 broadway) Robert Boyle (Sep 16)
- Re: Now:Power/Generators (Was: Re[2]: telehouse - 25 broadway) Lincoln Dale (Sep 16)
- Re: Now:Power/Generators (Was: Re[2]: telehouse - 25 broadway) David Lesher (Sep 16)