Re: Why choose 120 volts?


From: joel jaeggli <joelja () bogus com>
Date: Thu, 28 May 2009 08:20:36 -0700

If the pdu contains a surge suppressor and was designed for 120v, plugging in to 220 will cause the MOV that protects 
against transient over-voltage to emit smoke. The breaker or fuse is a current limiting device.

Joel

Pete Templin <petelists () templin org> wrote:

Dave Larter wrote:
Seems like if the c14 was connected to a 240v PDU the 5-15 would
deliver 240v to the equipment, arc/pop tripping the breaker on the
PDU as soon as it is connected killing power to everything on that
PDU.  Or am I missing something?

If you plug a PDU into a service that's higher voltage than expected, 
why would the PDU circuit breaker trip?  That breaker is measuring 
current, AFAICT, though in the end it might be measuring power. 
Regardless, it isn't measuring voltage, because that isn't constant 
(it's AC, after all) and is likely to drop under a short circuit, not 
skyrocket like the current will.