nanog mailing list archives

Re: Want to move to all 208V for server racks


From: Darren Bolding <darren () bolding org>
Date: Thu, 2 Dec 2010 13:42:45 -0800

One thing to be aware of- if you are going to be connecting gear with bigger
current draws- Cisco 6509's, most blade enclosures etc. come to mind- then
many of them effectively require 208V C19 connectors.

There are not as many power strips out there that provide sufficient numbers
of C19 connectors as would be desired, particularly if you want remote
switched power.

In that case 3 Phase power becomes more attractive.  Since many datacenters
are moving towards consolidation on Blades with SAN backend storage, it is
worth keeping in mind.

In the current DC's we support, we find the only need for 120V is for
laptops and such, which is solved by "convenience outlets" that are not on
the UPS plant.  We always get at least two 120V circuits just in case they
are needed, but haven't had any requirements for them recently.

--D

On Thu, Dec 2, 2010 at 1:22 PM, Steven Bellovin <smb () cs columbia edu> wrote:


On Dec 2, 2010, at 3:54 15PM, Jay Ashworth wrote:

----- Original Message -----
From: "Ingo Flaschberger" <if () xip at>

in europe GFIs are always needed for prection and by law.
to avoid the cascading effects the GFCIs are better.
break current ranges from 10mA (bath) up to 300mA; for servers I use
the 30mA with pulse protection (internal delay) to avoid the server
powersupply capacitor loading GFCIs "flip".

And that, indeed, is one of the circumstances in which Chris Lewis and
Steve Bellovin's Wiring FAQ suggests that you should *not* use a GFCI:
in places where the inevitable "nuisance trip" is troublesome, like
powering servers.

That FAQ is a bit dated, of course.

Indeed; it's been unmaintained for quite a number of years at this point.

The major place I personally have trouble with GFCIs is on things with
big motors, and in particular my basement dehumidifier -- a place I really
want a GFCI because we've occasionally had water problems...

And indeed, I never liked GFCI breakers for the usages for which they're
mandated in the US, cause the milliamp currents they're supposed to trip
on are no match for all that copper resistance...

Wire resistance shouldn't matter.  A GFCI is measuring the current in the
hot wire compared to the current in the neutral wire; if they differ by
more
than about 5 milliamps, the device trips.  That's why motors cause
problems:
the inductance of the windings can cause a brief current imbalance.

Anyway -- in response to the original question: the US electrical code
requires GFCI protection for outlets in kitchens, bathrooms, or unfinished
basements, for outdoor outlets, and for any other outlet near water.
 Canada
has slightly different rules, or at least it did when we last updated the
FAQ (Chris Lewis is Canadian): their code requires that every duplex
kitchen outlet be served by two separate circuits, which generally share a
common neutral.  A simple outlet GFCI can't handle that setup, since the
actual current flowing through the neutral will vary depending on the loads
on the two hot wires.  You'd need a specialized outlet or breaker GFCI that
summed the current across all three wires; such devices may exist but I've
never seen them.  (Btw -- the usual reason for using outlet GFCIs is that
they're much cheaper than breaker versions.)


               --Steve Bellovin, http://www.cs.columbia.edu/~smb









-- 
--  Darren Bolding                  --
--  darren () bolding org           --


Current thread: