Re: POE switches and lightning
From: Ingo Flaschberger <if () xip at>
Date: Sat, 15 May 2010 01:42:45 +0200 (CEST)
We had a lightning strike nearby yesterday that looks to have come inside our facility via a feeder circuit that goes outdoors underground to our facility's gate.
Perhaps there was a "move" of the earth-level relative to the neutral line. I have no idea how neutral-line to earth potential is handled in us, but here in austria we use a so called "nullung". That means that the earth-ground potential line of the building (which includes also the lightning conductor) is connected to the neutral power line where it enters the building, keeping this potential-difference low.
Theres also a potential between earth ground and the neutral-phase of the online-ups.
The ethernet-cables; utp or stp? pannels correctly earthed? Perhaps a electrician should check the earthing.Also all copper lines that enter the building should be protected by lightning protectors.
Kind regards,
Ingo Flaschberger
Current thread:
- POE switches and lightning Caleb Tennis (May 13)
- RE: POE switches and lightning Matlock, Kenneth L (May 13)
- Re: POE switches and lightning Larry Sheldon (May 13)
- Re: POE switches and lightning Pete Carah (May 13)
- Re: POE switches and lightning Daniel Senie (May 13)
- Re: POE switches and lightning Steven Bellovin (May 13)
- Re: POE switches and lightning Pete Carah (May 13)
- Re: POE switches and lightning Pete Carah (May 13)
- Re: POE switches and lightning Marshall Eubanks (May 14)
- Re: POE switches and lightning Ingo Flaschberger (May 14)
- Re: POE switches and lightning Seth Mattinen (May 14)
- Re: POE switches and lightning Larry Sheldon (May 14)