Re: Protecting 1Gb Ethernet From Lightning Strikes
From: Måns Nilsson <mansaxel () besserwisser org>
Date: Wed, 14 Aug 2019 13:02:25 +0200
Subject: Protecting 1Gb Ethernet From Lightning Strikes Date: Tue, Aug 13, 2019 at 02:22:12PM -0400 Quoting Javier J (javier () advancedmachines us):
I'm working with a client site that has been hit twice, very close by lightening. I did lots of electrical work/upgrades/grounding but now I want to focus on protecting Ethernet connections between core switching/other devices that can't be migrated to fiber optic.
If lightning comes so close that it will break things inside the same facility because they are connected by structured cabling, two things typically have failed; * The building as such is not adequately protected. * There exist too large potential differences within the electrical system inside the building. For #1, telecoms regulations on site grounding and protection give good, albeit expensive advice. The most important part is that all cabling enter the facility with its screens at common potential. The reason is that most blown equipment comes from in-ground potential difference between different cables. (I've poured shattered IC's out of a poor ADSL router after such a strike. ) If that potential difference is cancelled upon entry in the facility by bonding all grounds the risk is minimised. For #2, it is mostly solved by fixing #1, but it is proper to fix it by mesh-connecting grounds on all equipment together. If there is a 10mm^2 (around AWG7) bonding conductor parallel to the 0,14mm^2 (AWG25) drain wire in the foil screen, which way will the current take? Do note that star grounds are popular, but they're impossible to maintain and typically don't work at high frequiencies, which will lessen their efficiency against fast-rising transients. Mesh grounds are better at conducting high frequencies and are easier to maintain. Having several power utility feeds into same facility will of course exacerbate the problem, which is one of the reasons it is illegal in Sweden. If you need to cross between two buildings, copper should be rejected. Fiber is so much better. And pays for itself immediately upon first strike survived. /Måns, has 6 pairs 9/125 between garage and house at home. -- Måns Nilsson primary/secondary/besserwisser/machina MN-1334-RIPE SA0XLR +46 705 989668 I feel partially hydrogenated!
Attachment:
signature.asc
Description:
Current thread:
- Re: Protecting 1Gb Ethernet From Lightning Strikes, (continued)
- Re: Protecting 1Gb Ethernet From Lightning Strikes Bill Woodcock (Aug 13)
- Re: Protecting 1Gb Ethernet From Lightning Strikes Nate Burke (Aug 13)
- Re: Protecting 1Gb Ethernet From Lightning Strikes bzs (Aug 14)
- Re: Protecting 1Gb Ethernet From Lightning Strikes Chris Knipe (Aug 14)
- Re: Protecting 1Gb Ethernet From Lightning Strikes Mikael Abrahamsson (Aug 14)
- Re: Protecting 1Gb Ethernet From Lightning Strikes Nick Olsen (Aug 15)
- Re: Protecting 1Gb Ethernet From Lightning Strikes Jared Mauch (Aug 13)
- Re: Protecting 1Gb Ethernet From Lightning Strikes Bjørn Mork (Aug 14)
- Re: Protecting 1Gb Ethernet From Lightning Strikes Måns Nilsson (Aug 14)